Underground Car Park Fluid Separator
Monoblock vibrated reinforced concrete up to 500 parking spaces
with automatic shutter and UNI EN 858-1 compliant coalescence filter
Features and operating principle
Underground Car Park and Garage Oil Separators - precast concrete Fluid Separators for covered parking facilities for light fluids, oils and hydrocarbons are used specifically to collect and recover accidental oil and fuel leakages. Underground Car Park and Garage Oil Separators - Fluid Separators for covered parking facilities are equipped with a coalescence filter and a UNI EN 858 compliant automatic shutter. Underground Car Park and Garage Oil Separators - Fluid Separators for covered parking facilities are used to naturally separate sand, mineral oils and hydrocarbons in incoming wastewater, i.e. first rainwater from access ramps or floor washing.
Supply specifications
Delivery and Installation of an Underground Car Park and Garage Fluid Separator - up to 40 parking spaces - manufactured in DECLARED SERIES Mod. SEP____ external dimensions cm.____x___x h____ , parking spaces ____ , surface sqm.____ , manufactured EDIL IMPIANTI 2 S.r.l. with UNI EN ISO 9001 and ISO 45001 management system made of monoblock vibrated concrete, with CE-certified materials, concrete in compressive strength class C45/55 (RCK >55 N/mm²), internal improved-adhesion steel reinforcements checked in our plant, GREESMIX5® steel fibres (patent No. 0001421398 issued by the Ministry for Economic Development) and electro-welded square mesh B450C, with certification of CHEMICAL RESISTANCE and REACTION TO FIRE (Class A1) issued by an external body based on UNI EN standards.
The Fluid Separator for Underground Car Parks with up to 40 parking spaces is equipped with: inlets/outlets, internal partition wall, refillable inlet coalescence filter for oils and hydrocarbons with AISI 304 stainless steel frame.
Delivery and Installation of an Underground Car Park and Garage Fluid Mineral Oil Separator - up to 500 parking spaces - manufactured in DECLARED SERIES Mod. SEP____ external dimensions cm.____x___x h____ , parking spaces ____ , surface sqm.____ , manufactured EDIL IMPIANTI 2 S.r.l. with UNI EN ISO 9001 and ISO 45001 management system made of monoblock vibrated concrete, reinforced with vertical pillars and stainless steel horizontal beams, with CE-certified materials, concrete in compressive strength class C45/55 (RCK >55 N/mm²), internal improved-adhesion steel reinforcements checked in our plant, GREESMIX5® steel fibers (patent No. 0001421398 issued by the Ministry for Economic Development) and electro-welded square mesh B450C, with certification of CHEMICAL RESISTANCE and REACTION TO FIRE (Class A1) issued by an external body based on UNI EN standards.
The Mineral Oil Fluid Separator for Covered Parking Facilities up to 500 parking spaces is delivered with: inlets/outlets, sealed waterproof PVC sleeve with rubber gasket and AISI 304 stainless steel inlet deflector; AISI 304 stainless steel automatic shutter with outlet coalescence filter.
Underground Car Park Fluid Separator Dimensions
Download E.U. dimensions
Select Article Code to access the E.U. dimensions for the product.
Article Code
Data Sheet Download
Select Article Code to access the Data Sheet for the product.
Article Code
Fluid Separator for Underground Car Parks up to 45 parking spaces
Article Code |
Parking spaces N° |
Surface (mq) |
Pipes Diam. (mm) |
External Dimensions without cover slabs (cm) |
Separator Weight (ql) |
Cover slab weight (ql) | ||||
Width | Length | Height | h. 10 cm (B125) |
h. 15 cm (C250) |
h. 20 cm (D400) |
|||||
SEP10/20 | 10/20 | 500 | 110 | 70 | 70 | 90 | 4,3 | - | - | - |
SEP30 | 30 | 750 | 110 | 90 | 90 | 75 | 4,3 | - | - | - |
SEP40 | 40 | 1.000 | 110 | 90 | 90 | 100 | 5,6 | - | - | - |
SEP45 | 45 | 1.125 | 125 | 100 | 100 | 100 | 6,4 | 2,5 | 3,7 | 5,0 |
The data reported is purely indicative
Mineral Oil and Fluid Separator for Covered Parking Facilities up to 500 parking spaces
(excluding surface exposed to rain)
Article Code |
Parking spaces N° |
Surface (mq) |
Pipes Diam. (mm) |
External Dimensions without cover slabs (cm) |
Separator Weight (ql) |
Cover slab weight (ql) | ||||
Width | Length | Height | h. 10 cm (B125) |
h. 15 cm (C250) |
h. 20 cm (D400) |
|||||
SEP50 | 50 | 1.250 | 125 | 125 | 130 | 100 | 11,8 | 4,0 | 6,1 | 8,1 |
SEP60 | 60 | 1.500 | 125 | 125 | 130 | 150 | 15,6 | 4,0 | 6,1 | 8,1 |
SEP70 | 70 | 1.750 | 125 | 125 | 180 | 150 | 19,6 | 5,6 | 8,4 | 11,2 |
SEP100 | 100 | 2.500 | 125 | 175 | 180 | 130 | 21,7 | 7,8 | 11,7 | 15,6 |
SEP120 | 120 | 3.000 | 125 | 175 | 180 | 150 | 23,8 | 7,8 | 11,7 | 15,6 |
SEP150 | 150 | 3.750 | 160 | 180 | 240 | 150 | 47,1 | 10,7 | 16,1 | 21,5 |
SEP200 | 200 | 5.000 | 160 | 180 | 300 | 150 | 55,7 | 13,4 | 20,1 | 26,8 |
SEP250 | 250 | 6.250 | 200 | 246 | 270 | 200 | 78,3 | 16,5 | 24,7 | 33,0 |
SEP300 | 300 | 7.500 | 200 | 246 | 320 | 200 | 88,2 | 19,6 | 29,3 | 39,1 |
SEP400 | 400 | 10.000 | 200 | 246 | 370 | 200 | 98,1 | 22,6 | 33,9 | 45,2 |
SEP500 | 500 | 12.500 | 250 | 246 | 420 | 200 | 108,0 | 25,7 | 38,5 | 51,3 |
The data reported is purely indicative